1 2 3 4 5 6
ON
BATT
24V
EVAC
PA NE L N O
SILENCE
A
MPX
CN5
H8/3003
Standard Sub-panels
The Standard Sub-panel addresses and detector types are set using the DIP switches on the Sub-panel.
Each Sub-panel has an 6 way DIP switch. The first 5 switches set the panel number. Switch 6 (A) sets
the data protocol for the detectors fitted to the loops.
Note that addresses 01 and 02 are likely to be used by Integrated Sub-panels.
1 2 3 4 5 6
ON
PANEL NUMBER
A
PROTOCOL SWITCH A
Apollo Discovery™
Apollo Series 90 / XP95™ ™ 1
0
MANUFACTURER'S PROTOCOL SWITCH
6
A
SUB-PANEL NUMBER SWITCHES 1- 5
1-3
4-6
7-9
10-12
13-15
16-18
19-21
22-24
25-27
28-30
31-33
34-36
37-39
40-42
43-45
46-48
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
0 0 0 0 0
1 0 0 0 0
0 1 0 0 0
1 1 0 0 0
0 0 1 0 0
1 0 1 0 0
0 1 1 0 0
1 1 1 0 0
0 0 0 1 0
1 0 0 1 0
0 1 0 1 0
1 1 0 1 0
0 0 1 1 0
1 0 1 1 0
0 1 1 1 0
1 1 1 1 0
LOOP
Nº's
ADDRESS
SWITCH
1 2 3 4 5
COMMISSIONING
4000-SP
MAX 3A FAST ACTING