Learning Which Devices Are Fitted
Enter programming mode.
If site specific data has NOT been pre-programmed then select function 8-3-1 Clear Customer Flash
Memory and clear the customer flash. (You must NOT do this if you have been supplied with a SIM
CARD pre-programmed with your site data.)
Select function 8-3-2 Clear Non-Volatile RAM and clear the NVRAM.
Exit Programming mode.
Press SYSTEM RESET.
Wait 90 seconds for the system to automatically learn which devices are present, program any
Discovery™ devices and report any faults.
(A SYSTEM RESET or Master Reset in Installation Mode results in an analogue loop power off period
of 8 seconds [reset], an analogue loop charge up of 15 seconds then commencement of loop polling.
30 seconds after polling has started the Discovery™ detectors are written to to set their LED ‘flash
when polled’ status and their sensitivity mode. This takes up to 30 seconds. The initial 30 second wait
is necessary to learn the presence of the devices before they can be written to.)
Review the faults (using the FAULT (QUEUE REVIEW) key if there is more than one). Note down the
messages then remove power and rectify the faults.
Power up the system, let it initialize and enter programming mode.
Select function 7-1 Device Count, Type and Value
Using the +/- keys to select the loop number and 0-9 or to select the device confirm that all
Sub-panels and devices are present.
Once all faults have been cleared and the system has been in Installation Mode for 90 seconds then
the system can be put into Active Mode.
Note that there is no clear end to Installation mode because the system is constantly looking and
learning. However if the system is put into Active Mode and Installation Mode hasn’t had time to
identify all system components you will very quickly be greeted with error reports regarding unexpected
devices.
If devices are ever removed, replaced or added then Installation Mode must be selected so that the
system can learn the new configuration. If you do not do this the system will report a fault.
New SAM’s (Self Addressable Modules) need a different installation process because they
need to be assigned addresses before the panel can learn that they are present. This procedure is
covered later in this manual in the section entitled “6-4 Automatic Address Setting (SAM)”.
Note -
COMMISSIONING