Sounder Audibility Check
If the building is unoccupied then press SOUND ALARMS. All sounders should operate until the button
is pressed again. Confirm that this is the case.
Note that Apollo loop sounders may take a second or two to respond.
If the building is occupied it is strongly recommended that the test sounders functions in programming
mode are used. Enter programming mode and select 7-2 Test Sounders. Using this function, all the
sounders can be checked.
The Main Panel Conventional Sounders will sound for 1 second then be silenced for 9 seconds.
Conventional Sounders and Loop Sounders are operated for 1 second then silenced for 9 seconds.
Note that the Loop Sounder operation is not synchronized to the loop sounder polling so the sounder
operation may sound a little intermittent - this is OK.
Conventional Sounder operation for a Repeater with Integrated Sub-panel will be synchronized to the
Loop Sounder operation.
Main Panel
Standard Sub-panels
Integrated Sub-panels
Conventional Sounders and Loop Sounders are operated for 1 second then silenced for 9 seconds.
COMMISSIONING