Setting Panel Addresses And Types
Each Repeater and Sub-panel needs a unique address.
Each Repeater and Sub-panel also needs the detector type set.
This has a fixed address of 01.
The default detector type is Apollo discovery™ . In this mode all Apollo protocol devices (S90 ,
XP95 Discovery ) are supported. (It is possible to change the detector type to Apollo
S90 /XP95 only but this is rarely necessary.)
Main Panel Integrated Sub-panel
™ ™
™ and ™
™ ™
™
™
Repeater Integrated Sub-panel
The default address for the Integrated Sub-panel on a Repeater is 02.
To set up the Integrated Sub-panel on a Repeater firmly depress the TEST (QUEUE REVIEW) and
DISABLED (QUEUE REVIEW) buttons on the Repeater while powering up.
This will power the Repeater up in REPEATER INSTALL MODE. If it does not, try again, the buttons
must be firmly held down during the power up process.
Once in REPEATER INSTALL MODE the following options are available:
Press SOUND ALARMS to clear the NVRAM
If the system has not been commissioned or installed then it is recommended to clear the NVRAM.
Note that this will also set the panel number back to 02 and the panel type to DISCOVERY .
If the system has been installed then clearing the Repeater NVRAM will clear all the installation
information and the SYSTEM be put into INSTALLATION MODE to re-learn the fitted devices. A
Main Panel Master Reset also be performed so that all system settings are re-sent to all
Repeaters and Sub-panels.
If the panel number is changed the SYSTEM also be put into INSTALLATION MODE to learn the
new panel number.
The default detector type is
Apollo Discovery .
Press FIRE (QUEUE REVIEW) to increment the panel number
Press FAULT (QUEUE REVIEW) to decrement the panel number
Press TEST (QUEUE REVIEW) to step through the available detector types
Press SYSTEM RESET to save and exit REPEATER INSTALL MODE
must
must
must
COMMISSIONING