Code Alarm F60 Instruções de Operação

Consulte online ou descarregue Instruções de Operação para Sistemas de ignição com controlo remoto Code Alarm F60. Code Alarm F60 Operating instructions Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 8
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
EC3 Series
Coldroom Controllers
D A T A S H E E T
EC3-3_35041_EN_R13.docx 1 / 8 23.02.2012
The
EC3
-
33x
Series form a new generation of electronic
controllers for refrigeration and air conditioning.
The controllers feature a DIN rail mounted housing and a
separate optional display unit in the small industry standard
housing form factor. They off
er maximum functionality such as
superheat, temperature and defrost controller with built-
in
TCP/IP Ethernet
functionality. Any standard WebBrowser (e.g. Internet
Explorer
®
or Mozilla Firefox) can be used for monitoring or
parameter setting.
The version with Echelon LON
®
network interface is for use in
more complex systems, where different controllers must
communicate with each other.
Features
Superheat control with self-adapting algorithm and driver
circuit for stepper motor driven Electrical Control Valves
EX4 … EX8
Air temperature control
Defrost and fan management
Limitation of evaporating pressure (MOP)
Feed-through of 4 … 20mA signal of evaporating pressure
transmitter to analogue output to operate multiple
controllers with a common pressure transmitter
2 digital inputs for compressor safety loop and coldroom
door contact
4 relay outputs for compressor, fan, defrost and alarm
Support of two network technologies:
TCP/IP Ethernet with WebServer functionality allows
monitoring and configuration of controllers through a
standard WebBrowser (e.g. Internet Explorer
®
or Mozilla
Firefox)
or Echelon FTT10 LON
®
technology for monitoring and
configuration through a supervisory system such as the
ALCO Monitoring Server EMS
Alarm messaging by email (EC3-332)
Integral backup battery to close Electrical Control Valve in
case of power loss
Electrical connection via plug-in type screw terminals
Aluminum housing for DIN rail mounting
Features ECD-001 Display Unit
Front panel mounted human interface for parameter and
status read-out and controller setup via keypad
digit LED display with automatic decimal point
Indicator LEDs for compressor, fan, heater and alarm
Connection to EC3 Series via ECC-N10 or standard CAT5
patch cord with RJ45 connectors.
Standard 71 x 29 mm cut-out dimensions
IP65 protection class when mounted in front panel
Typical ordering package:
EC3-332 Coldroom Controller with K03-330 Terminal Kit
EX5-U21 Electrical Control Valve with EX5-N30 Cable
ECD-001 Display Unit with ECC-N10 Cable
ECT-323 Transformer
PT5-07M Pressure Transmitter with PT4-M30 Cable
ECN-S30 Air Temperature Sensor
ECN-N30 Pipe Temperature Sensor
ECN-F60 Fin Temperature Sensor
Selection Table Coldroom Controller
TCP/IP Ethernet
LON
®
FT
T
Description Type Part No.
single unit
Part No.
Kit*
Type Part No.
single unit
Part No.
Kit*
Coldroom Controller ECV Stepper Motor Drive
EC3
-
332
807 632 808 013
EC3
-
331
807 631 808 012
*) Kit contains terminal kit, pressure transmitter PT5-07M with cable assembly, transformer 25VA, NTC sensors 6m fin, pipe and single insulated version
EC3 Series Coldroom Controller
with ECD-001 Display Unit
Vista de página 0
1 2 3 4 5 6 7 8

Resumo do Conteúdo

Página 1 - Coldroom Controllers

EC3 Series Coldroom Controllers D A T A S H E E T EC3-3_35041_EN_R13.docx 1 / 8 23.02.2012 The EC3-33x Series form a

Página 2

EC3 Series Coldroom Controllers D A T A S H E E T EC3-3_35041_EN_R13.docx 2 / 8 23.02.2012 Introduction The EC3-33x ser

Página 3

EC3 Series Coldroom Controllers D A T A S H E E T EC3-3_35041_EN_R13.docx 3 / 8 23.02.2012 Defrost EC3-33x Series contr

Página 4

EC3 Series Coldroom Controllers D A T A S H E E T EC3-3_35041_EN_R13.docx 4 / 8 23.02.2012 The top fields indicate the

Página 5

EC3 Series Coldroom Controllers D A T A S H E E T EC3-3_35041_EN_R13.docx 5 / 8 23.02.2012 Alarm and Maintenance Function

Página 6

EC3 Series Coldroom Controllers D A T A S H E E T EC3-3_35041_EN_R13.docx 6 / 8 23.02.2012 Accessories Terminal Kits for

Página 7

EC3 Series Coldroom Controllers D A T A S H E E T EC3-3_35041_EN_R13.docx 7 / 8 23.02.2012 Technical Data EC3 Series Contr

Página 8

EC3 Series Coldroom Controllers D A T A S H E E T EC3-3_35041_EN_R13.docx 8 / 8 23.02.2012 Physical Dimensions Drawings (m