MultiZone Gas Monitors • HGM-MZ (Halogen) • AGM-MZ (Ammonia) • CO2-MZ (Carbon Dioxide) Installation • Operation • Maintenance
Multi-Zone Gas Monitors 4 P/N: 3015-5074 Rev 13 An audible alarm and front panel indicators are provided to signal alarm and fault conditions, and
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 5 DO NOT block any of the zones. Unused zones may be disabled by setting the distance parameter to z
Multi-Zone Gas Monitors 6 P/N: 3015-5074 Rev 13 NOTE: The pickup points located on the floor in the above illustration are examples for refrigera
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 7 General Multi-Zone Specifications Coverage 4 point standard, expandable to 16 points in 4 point inc
Multi-Zone Gas Monitors 8 P/N: 3015-5074 Rev 13 SECTION 2. INSTALLATION 2.1. Installation Considerations 2.1.1. Warnings and Cautions WARNING
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 9 The enclosure utilizes keyhole mounting brackets designed for ¼ inch fasteners. Locate the four sc
Multi-Zone Gas Monitors 10 P/N: 3015-5074 Rev 13 Figure 2-2. MZ Monitor Side View 2.2.2. Tubing Considerations Use ¼” (6.35 mm) outside diameter
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 11 with the Halogen Gas Monitor to filter refrigerant from the purge line. It may be mounted adjacen
Multi-Zone Gas Monitors 12 P/N: 3015-5074 Rev 13 2.2.6. Installing an Optional Splitter Kit Splitter kits are made available which allow the MZ un
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 13 2.3. Interior Components Figure 2-4. MZ Monitor Interior Components NOTE: The plastic cabl
Multi-Zone Gas Monitors ii P/N: 3015-5074 Rev 13 WARRANTY Bacharach, Inc. warrants to Buyer that at the time of delivery this Product will be free
Multi-Zone Gas Monitors 14 P/N: 3015-5074 Rev 13 WARNING: Copper conductors for connection to supply mains must be made in accordance with NEC/C
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 15 2.5.1. Remote Display Module (RD) Connection The MZ is connected to the optional RD using a shiel
Multi-Zone Gas Monitors 16 P/N: 3015-5074 Rev 13 2.5.4. Changing Terminator Switch Settings The terminator switch is shipped from the factory in t
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 17 2.6. Terminating Multiple Monitors Figure 2-8. Termination Settings for a Network of Multiple M
Multi-Zone Gas Monitors 18 P/N: 3015-5074 Rev 13 NOTE: User must have two (2) dedicated ports to successfully complete the required setup. Figu
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 19 NOTE: The PC software is not compatible with 64-bit (or newer) computers. NOTE: The PC software
Multi-Zone Gas Monitors 20 P/N: 3015-5074 Rev 13 IMPORTANT: When a modified parameter (zone, system, or calibration) is sent to the MZ monitor, p
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 21 2.9. Optional Current Loop Interfaces NOTE: The two-output, current loop interface is an option
Multi-Zone Gas Monitors 22 P/N: 3015-5074 Rev 13 2.9.2. 4-20 mA DC Connections External devices are connected to the MZ monitor using a shielded d
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 23 Figure 2-12. Optional Dual 4-20 mA DC Output Board and Connector 2.10. Connecting External Alarm
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 iii Table of Contents SECTION 1. INTRODUCTION...
Multi-Zone Gas Monitors 24 P/N: 3015-5074 Rev 13 Jumper the “Live/Positive” line of an external power source (DC devices) or the monitor’s AC input
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 25 SECTION 3. SETUP PROGRAMMING 3.1. Initial Power Up When the MZ monitor is powered up, all front
Multi-Zone Gas Monitors 26 P/N: 3015-5074 Rev 13 Figure 3-3. HGM System Setup Screen #2 3.4.1. Location This is the name you assign to the MZ mo
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 27 3.4.5. Zone Hold Sets the length of time a zone will be monitored when the zone hold feature is a
Multi-Zone Gas Monitors 28 P/N: 3015-5074 Rev 13 3.4.9. Re-Zero Mode This parameter defines the frequency at which the instrument re-zeros the opt
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 29 2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to m
Multi-Zone Gas Monitors 30 P/N: 3015-5074 Rev 13 3.6.3. Node Address Each monitor on the network must has a distinct node address. The node addre
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 31 SECTION 4. GENERAL OPERATION 4.1. Functional Overview Normally each MZ monitor will sequentially
Multi-Zone Gas Monitors 32 P/N: 3015-5074 Rev 13 4.2.3. Distance + EXH This parameter defines the combined length of the sample tubing plus any t
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 33 4.3.1. Leak Level This is the concentration level in PPM that will activate a leak alarm conditio
Multi-Zone Gas Monitors iv P/N: 3015-5074 Rev 13 2.8.2. Saving and Sending Programs ...
Multi-Zone Gas Monitors 34 P/N: 3015-5074 Rev 13 4.4.2. Responding to Alarms An operator can respond to the alarms by accessing the Alarm Summary
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 35 This screen provides the following navigation options at the bottom of the display: ACK Using the
Multi-Zone Gas Monitors 36 P/N: 3015-5074 Rev 13 4.4.6. Clearing the Alarm Event Log A data log of the last 20 alarm events is retained in memory.
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 37 4.5.2. Navigating to the Fault Screen Displayed on the initial Data Display Screen is a Fault opt
Multi-Zone Gas Monitors 38 P/N: 3015-5074 Rev 13 4.5.4. Non Critical Faults Fault Code Description / Possible Causes BOX TEMP FAULT <0001>
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 39 4.5.7. Viewing Fault Log A data log of the last 20 fault conditions is retained in memory. On the
Multi-Zone Gas Monitors 40 P/N: 3015-5074 Rev 13 This screen lists the zones in the left column and displays flow data. Use the UP/DOWN buttons to
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 41 IMPORTANT: Changing information on CAL FACTOR will void the factory calibration. Typically, the
Multi-Zone Gas Monitors 42 P/N: 3015-5074 Rev 13 NOTE: The CO2 calibration is a more complex, 2-point calibration. CO2 units are factory calibr
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 43 Program the instrument for a new gas as follows: 1. From the Calibration Screen, use the PREV GAS
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 v 4.4.1. Functional Overview ...
Multi-Zone Gas Monitors 44 P/N: 3015-5074 Rev 13 4.9. The Diagnostic Screen 4.9.1. Navigating to the Diagnostic Screen On the System Setup screen
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 45 4.9.2. Diagnostic Screen Overview The Diagnostic Screen contains sensor data and status informati
Multi-Zone Gas Monitors 46 P/N: 3015-5074 Rev 13
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 47 SECTION 5. MAINTENANCE WARNING: Shock hazard! Always disconnect AC power before opening the enc
Multi-Zone Gas Monitors 48 P/N: 3015-5074 Rev 13 Part Name P/N Description Water Trap 0007-1655 The water trap removes moisture that enters tubi
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 49 Item Description Part Number ¼” to 6 mm Reducer Kit (10) 3015-5389 (10) ¼” to 6 mm Reducer Kit (8
Multi-Zone Gas Monitors 50 P/N: 3015-5074 Rev 13 Item Description Part Number 12 Zone (13 line end filters, 1 charcoal filter, 1 hydrophobic,
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 51 Figure 5-1. Sample DIGIPOT Readings 8. Scroll to “DET DIGIPOT” option (see
Multi-Zone Gas Monitors 52 P/N: 3015-5074 Rev 13
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 53 APPENDIX A. RECOMMENDED REFRIGERANT GAS ALARM SETTINGS Gas Alarm Settings (PPM) Gas
Multi-Zone Gas Monitors vi P/N: 3015-5074 Rev 13 B.5.6. Alarms and Alarm Acknowledge ...
Multi-Zone Gas Monitors 54 P/N: 3015-5074 Rev 13
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 55 APPENDIX B. RS-485 COMMUNICATIONS PROTOCOL B.1. Overview The following instructions are intende
Multi-Zone Gas Monitors 56 P/N: 3015-5074 Rev 13 IMPORTANT: Each time parameters are modified and sent back to the monitor using function 16 (pre
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 57 NOTE: All data sent out from the MZ is in “little endian” byte order (least significant byte fol
Multi-Zone Gas Monitors 58 P/N: 3015-5074 Rev 13 B.4. Standard Register Summary B.4.1. Dynamic Register Summary (2000 Series; R; Function Code 03
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 59 Register Address Description Type Range 2036 (STATUS) ACTIVE ZONE UNSIGNED INT 1-16 2037 (ST
Multi-Zone Gas Monitors 60 P/N: 3015-5074 Rev 13 Register Address Description Type Range 3016 LEAK LEVEL ZONE 1 UNSIGNED INT >0 <SPILL P
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 61 Register Address Description Type Range 3055 EVAC LEVEL ZONE 8 UNSIGNED INT >SPILL -10K PP
Multi-Zone Gas Monitors 62 P/N: 3015-5074 Rev 13 Register Address Description Type Range 3094 ALARM ACK ZONE 15 UNSIGNED INT 1=ACK 0=NACK 3095
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 63 Variable Type Length Description Aud_Alarm UC 1 byte Sounds internal board buzzer on conditio
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 1 SECTION 1. INTRODUCTION 1.1. About This Manual Thank you for investing in a Bacharach Multi-Zone
Multi-Zone Gas Monitors 64 P/N: 3015-5074 Rev 13 B.5.4. Fault Code Table BIT Fault Type Code Description 15 CLIPPING FAULT 0x8000 0x8000 Se
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 65 NOTE: Refer to the Recommended Alarm Settings & Gas Enumeration table on page 53. NOTE: T
Multi-Zone Gas Monitors 66 P/N: 3015-5074 Rev 13 B.5.8. Sensor Data Register 0x0016h (22 Dec) (R, 82 Bytes) Variable Type Length Description Pr
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 67 B.5.12. Fault Log Register 0x1900-01 (6400-6401 Dec) (R, 302 Bytes) These registers contain the 2
Multi-Zone Gas Monitors 68 P/N: 3015-5074 Rev 13 B.5.17. MZ Service Mode The MZ monitor can be placed into service mode if necessary. During servi
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 69 APPENDIX C. SYSTEM MENU MAP
Multi-Zone Gas Monitors 70 P/N: 3015-5074 Rev 13
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 71 APPENDIX D. AGENCY APPROVALS
Multi-Zone Gas Monitors 72 P/N: 3015-5074 Rev 13
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 73 European Standard EN14624: 2005 testing with R-134a (Halogen Gas Monitor Only). Min. Sensitivit
Multi-Zone Gas Monitors 2 P/N: 3015-5074 Rev 13 WARNING: A switch or circuit breaker must be included in the building installation. The switch m
Multi-Zone Gas Monitors 74 P/N: 3015-5074 Rev 13
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 75 APPENDIX E. SERVICE CENTERS United States Bacharach, Inc. 621 Hunt Valley Circle New Kensington
Multi-Zone Gas Monitors 76 P/N: 3015-5074 Rev 13
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 77 INDEX NUMBERS 0007-1650 ... 47, 48 0007-1655 ...
Multi-Zone Gas Monitors 78 P/N: 3015-5074 Rev 13 B Bacharach service center ... 3, 9 website...
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 79 filter(s) ... iii, 4, 5, 11, 12, 37, 47-54, 63 replacement ...
Multi-Zone Gas Monitors 80 P/N: 3015-5074 Rev 13 N N7100 ... 6, 57, 68 N7200 ...
Multi-Zone Gas Monitors P/N: 3015-5074 Rev 13 81 service ... ii, 5, 13, 15, 16, 22, 23, 29, 61, 62, 67 centers ...